Configuring Ethernet connection, LOGO! to HMI devices

When you need to connect a Siemens HMI (SIMATIC Panel) device to a LOGO! Base module, you can only connect them through drag-and-drop.

Double-click the connection line to configure the connection settings:

LOGO! Base Module:

All the fields are read-only.

The LOGO! Base Module is always the server.

HMI:

You can set the TSAP address here. Or it shows the TSAP of the starting point of your connection.

Data transfer table

Select the "Add data transfer information" check box to activate the data transfer table.

See Tools -> Ethernet Connections (0BA7 and later versions only) for more information about data transfer configurations.

Note

The LOGO! Base Module is always the server in a connection between a LOGO! Base Module and an HMI device. A LOGO! device can only connect to one HMI.